Series CMT8

Three-phase isolation transformer for medical use UCC > 8%

Series CMT8

Three-phase isolation transformer for medical use UCC > 8%

Three-phase transformer with galvanic isolation between primary and secondary, for supply in medical installations (operating theatres, ICU, ICU) in accordance with the mandatory requirements of the IEC/UNE-EN 61558-2-15 standard.

Electrostatic shield between primary and secondary connected to a separate terminal which attenuates electrical disturbances from the mains to medical equipment.

High impedance with short-circuit voltage >8%, allowing the primary circuit breakers to be set to the next higher nominal current value.

Features

  • Generates the IT neutral regime in installations with interruption-sensitive processes.
  • Built-in NC contact thermal protector (250V 6A). In the event of overtemperature or overload, it opens the circuit and alerts the safety monitor. Automatically resets when an anomaly disappears.
  • Robust and complete varnishing protects against humidity, dust and corrosion.
  • IP20 terminal connection protects against direct voltage contact.
  • Magnetic core with low loss and low Inrush current.

Specifications

Power 1 ÷ 10 kVA
PRI Voltage 3 x 400 V
SEC Voltage 3 x 230 V
Frequency 50/60 Hz
Ambient Temperature 40 ºC
Thermic Class F (155 ºC)
PI IP00
Electric Shock Protection Class I
Test Voltage 4 kV - 2 kV
Connection current < 8 In
Empty PRI voltage < 3%
Shortcircuit Voltage > 8,5%
Leakage Current < 40 µ
Isolation resistance > 7 MΩ
Regulations IEC/UNE-EN 61558-1
IEC/UNE-EN 61558-2-15

Quality Seals

Marcado CE

UK-CA

Uses

For general use as isolation transformer for IT generation in medical installations (operating theatres, ICU, ICU).

Protection of medical equipment sensitive to electrical disturbances.

* TORYTRANS reserves the right to modify the information in any time and without prior notice. Design, dimensions or weight of the product could be different.