Series MT

Instrument transformer

Series MT

Instrument transformer

Voltage measuring transformers to reduce the high value of the voltage to be measured to a small, safe value that is easy to handle for relays, analysers and measuring equipment.

The accuracy class indicates the maximum voltage error in the transformation ratio.

Class 0.5: error <0.5% at the indicated power.

Class 1: error <1% at the indicated power

Features

  • Enclosure made of self-extinguishing V0 technical polyamide, halogen and phosphor free.
  • To isolate and separate circuits and measuring equipment from high-voltage lines.
  • Screw connection and pre-inserted thrust washer.
  • Highly accurate transformer ratio even with voltage and current transients.
  • Protects the user from access to dangerous contact parts of the winding.

Specifications

Power 3 ÷ 150 VA (Clase 0,5)
3 ÷ 250 VA (Clase 1)
PRI Voltage max. 690 V/√
SEC Voltage 100 V/√3
Frequency 50/60 Hz
Ambient Temperature 40 ºC
Thermic Class F (155 ºC)
PI IP20
Output Accuracy Class 0,5
Class 1
Electric Shock Protection Class II
Test Voltage 4kV
Regulations IEC/UNE-EN 61869-3

Quality Seals

Marcado CE

UK-CA

Uses

Class 0,5: Precision and pricing equipment.

Class 1: Industrial measuring equipment

Technical data references

Data

Dimensions

* TORYTRANS reserves the right to modify the information in any time and without prior notice. Design, dimensions or weight of the product could be different.