Passive harmonic filter especially designed for 6 pulses power converters such as frequency converters, variable speed drives for motors, three phase rectifiers, battery chargers, HVAC systems, etc. Protection degree IP20.
Motor rating | 4 ÷ 220 kW (5,5 ÷ 300 CV) |
Nominal current | 9 ÷ 408 A |
Nominal voltage | 3 x 400 V ± 20 V |
Frequency | 50 Hz |
Harmonic order filtering | 3º, 5º, 7º, 11º, 13º |
Load distortion 75-100% | ≈ 5 % THD-I |
Load distortion 50-75% | ≈ 6 % THD-I |
Load distortion< 50% | ≈ 8 % THD-I |
Load 100 % power factor | ≥ 0,99 |
* with load > 40% | ≥ 0,9 |
Ambient Temp. | 30 ºC |
Protection degree | IP-20 |
Cooling | Natural air |
Marked | CE |
Standard | IEC/UNE-EN 60076-6 IEC/UNE-EN 61006-6 |
642 KB
* TORYTRANS reserves the right to modify the information in any time
and without prior notice. Design, dimensions or weight of the product could be different. *
SPF004 | SPF005 | SPF007 | SPF011 | SPF015 | SPF018 | SPF022 | SPF030 | SPF037 | SPF045 | SPF055 | SPF075 | SPF090 | SPF110 | SPF132 | SPF150 | SPF160 | SPF185 | SPF200 | SPF220 | |
Request offer | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request |
Power (kW) | 4 | 5,5 | 7,5 | 11 | 15 | 18,5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | 110 | 132 | 150 | 160 | 185 | 200 | 220 |
Power (CV) | 5,5 | 7,5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 | 150 | 180 | 205 | 220 | 270 | 270 | 300 |
Current (A) | 9 | 12 | 16 | 23 | 30 | 37 | 43 | 58 | 72 | 86 | 104 | 140 | 168 | 204 | 245 | 278 | 296 | 341 | 369 | 406 |
Losses (W) | 165 | 190 | 225 | 310 | 350 | 405 | 450 | 565 | 610 | 670 | 720 | 975 | 1145 | 1345 | 1435 | 1505 | 1610 | 1660 | 1835 | 1835 |
IP | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
Phases | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase |
Use | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD |
Ambient temperature | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC | 30ºC |
Electric shock protection | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I |
Converter voltage | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V |
A | 290 | 290 | 290 | 330 | 330 | 330 | 330 | 410 | 410 | 410 | 410 | 490 | 490 | 570 | 570 | 570 | 570 | 570 | 570 | 570 |
B | 250 | 250 | 250 | 315 | 315 | 315 | 315 | 390 | 390 | 390 | 390 | 410 | 410 | 470 | 470 | 470 | 470 | 470 | 470 | 470 |
C | 510 | 510 | 510 | 610 | 610 | 610 | 610 | 670 | 670 | 670 | 670 | 1275 | 1275 | 1520 | 1520 | 1520 | 1520 | 1520 | 1520 | 1520 |
Weight (Kg) | 21,0 | 24,6 | 27,2 | 34,3 | 40,7 | 50,4 | 56,0 | 66,2 | 84,5 | 94,4 | 105 | 129 | 147 | 193 | 222 | 235 | 269 | 298 | 320 | 356 |
Type | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |