Passive harmonic filter designed for 6 pulses power converters such as frequency converters, variable speed drives for motors, three phase rectifiers, battery chargers, HVAC systems, etc. Protection degree IP-00 with epoxy barnish. Optionally, a contactor can be incorporated, that according to the converter load level, the reactive part of the filter can be switched off when no-load.
Motor rating | 4 ÷ 220 kW (5,5 ÷ 300 CV) |
Nominal current | 9 ÷ 408 A |
Nominal voltage | 3 x 400 V ± 20 V |
Frequency | 50 Hz |
Harmonic order filtering | 3º, 5º, 7º, 11º, 13º |
Load distortion 75-100% | aprox 5 % THD-I |
Load distortion 50-75% | aprox 6 % THD-I |
Load distortion < 50% | aprox 8 % THD-I |
Load 100% power factor | aprox 0,99 |
* with load > 40% | aprox 0,9 |
Ambient temp. | 40 ºC |
Protection degree | IP-00 |
Cooling | Natural air |
Marked | CE |
Standard | IEC/UNE-EN 60076-6 IEC/UNE-EN 61006-6 |
349 KB
* TORYTRANS reserves the right to modify the information in any time
and without prior notice. Design, dimensions or weight of the product could be different. *
SPFS004 | SPFS005 | SPFS007 | SPFS011 | SPFS015 | SPFS018 | SPFS022 | SPFS030 | SPFS037 | SPFS045 | SPFS055 | SPFS075 | SPFS090 | SPFS110 | SPFS132 | SPFS150 | SPFS160 | SPFS185 | SPFS200 | SPFS220 | |
Request offer | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request | Request |
Power (kW) | 4 | 5,5 | 7,5 | 11 | 15 | 18,5 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | 110 | 132 | 150 | 160 | 185 | 200 | 220 |
Power (CV) | 5,5 | 7,5 | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 | 75 | 100 | 125 | 150 | 180 | 205 | 220 | 270 | 270 | 300 |
Current (A) | 9 | 12 | 16 | 23 | 30 | 37 | 43 | 58 | 72 | 86 | 104 | 140 | 168 | 204 | 245 | 278 | 296 | 341 | 369 | 406 |
Losses (W) | 165 | 190 | 225 | 310 | 350 | 405 | 450 | 565 | 610 | 670 | 720 | 975 | 1145 | 1345 | 1435 | 1505 | 1610 | 1660 | 1835 | 1835 |
IP | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Phases | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase | Three-phase |
Use | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD | Line for VFD |
Ambient temperature | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC | 40ºC |
Electric shock protection | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I | Classe I |
Converter voltage | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V | 380V ÷ 420V |
A | 210 | 210 | 210 | 260 | 260 | 260 | 260 | 320 | 320 | 320 | 320 | 490 | 490 | 570 | 570 | 570 | 570 | 570 | 570 | 570 |
B | 205 | 210 | 225 | 245 | 250 | 265 | 280 | 330 | 335 | 350 | 360 | 370 | 370 | 370 | 400 | 400 | 420 | 420 | 440 | 440 |
C | 410 | 410 | 410 | 510 | 510 | 510 | 510 | 570 | 570 | 570 | 570 | 1275 | 1275 | 1520 | 1520 | 1520 | 1520 | 1520 | 1520 | 1520 |
Weight (Kg) | 14 | 16 | 20 | 25 | 30 | 38 | 46 | 59 | 65 | 78 | 87 | 108 | 130 | 151 | 193 | 199 | 227 | 236 | 263 | 271 |
Type | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |